Arctic Refrigeration Components Supply Sdn Bhd is authorised distributor for Kriwan in Malaysia,Singapore, Indonesia,Vietnam,Thailand,Philippines,Cambodia, Myanmar(Burma),Laos,Brunei,India,Pakistan,Sri Lanka, Bangladesh,Middle East, Arica & Asia....
KRIWAN INT69 B2 MOTOR PROTECTOR (Parts No. 22A608) Application : The INT69 B2 motor protector has been developed especially for use in cases with a higher starting load or for drives with a high switching frequency. Functional description :
At the measuring circuit input of the INT69 B2 (orange wires), it is possible to connect up to nine DIN 44081/082- conform PTC sensors. Sensors with different nominal response temperatures may be used. Thus it is possible to monitor several measuring points with only one INT69 B2 motor protector.
If the temperature in one of the monitored parts or sections exceeds the nominal response temperature of the respective PTC sensor, the sensor becomes highly resistive and the motor protector switches off. After cooldown, restarting is only possible if the electronic lock of the output relay is released by interrupting the voltage supply. Ex works the lock-out bridge is installed at terminals B1-B2. Alternatively the locked version can be changed to an unlocked version by removing bridge B1-B2. In that case the device switches itself on again after the cooldown.
The relay switch output is designed as a potential free change-over contact. This switching circuit function according to the closed-circuit principle, i.e. the relay drops back to the reset position also in case of sensor or cable failure and shuts off. The sensor, relay and supply circuits are galvanically isolated from each other. |
PRODUCT DETAILS | |
Supply voltage | AC 115-230V Hose Power : 15 - 40 |
Permitted ambient temperature | -30...+70°C |
Temperature measuring circuits: Type | 1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series |
Temperature measuring circuits: R_25, total | <1.8kΩ |
Temperature measuring circuits: R_trip | 4.5kΩ ±20% |
Temperature measuring circuits: R_trip, static | 4.5kΩ ±20% |
Temperature measuring circuits: R_reset | 2.75kΩ ±20% |
Temperature measuring circuits: Max. length connection line | 30m |
Resetting the lock | Main reset >5s only possible if there is no error current |
Relay: Connection | AC 240V 2.5A C300 at least AC/DC 24V 20mA |
Relay: Mechanical service life | Approx. 1 million switching cycles |
Protection class acc. To EN 60529 | IP00 |
Connection type | Flat plug sleeves (PTC), screw terminals |
Housing material | PA glass-fibre-reinforced |
Mounting | Can be snapped onto 35mm standard rail acc. to EN 60715 or screw mounted |
Dimensions | Refer to dimensions in mm |
Weight | Approx. 200g |
Check base | EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2 |
Approval | UL File No. E75899 cURus |
Inquiry - Kriwan INT69 B2 (22A608)